weg
WEG DWE-4 Advanced Electronic Motor Protection Relay
Model: DWE-4-S4-MT
4-hour response · Pricing in SAR · Delivery across all KSA regions
WEG DWE-4 Advanced Electronic Motor Protection Relay
The WEG DWE-4 is the advanced tier of WEG's electronic motor protection relay range, offering expanded protection functions, higher measurement accuracy, and advanced communication options beyond the DWE-3 platform. Designed for large and critical motors in Saudi Aramco oil and gas facilities, SABIC mega-complexes, SWCC desalination stations, and SEC power generation plants, the DWE-4 provides comprehensive motor protection that extends motor service life, reduces unplanned downtime, and provides detailed diagnostic data for predictive maintenance programmes increasingly adopted by Saudi industrial operators under Vision 2030's industrial transformation initiatives.
Advanced Protection Functions
The DWE-4 provides all DWE-3 protection functions plus: voltage-based protection (over/under voltage trip), power factor monitoring, active and reactive power measurement, starting current profile recording, event log (last 8 fault events with time stamps), and harmonic content monitoring (THD). These additional functions are specified by Saudi Aramco for motors on critical services where detailed post-trip analysis is required, and by SABIC for motors integrated with plant-wide energy management systems.
Communication and Integration
The DWE-4 supports Modbus RTU and optionally PROFIBUS DP, allowing integration with both legacy Aramco SCADA systems (Modbus-based) and modern PROFIBUS-equipped DCS platforms such as ABB 800xA and Siemens PCS 7 used in Saudi Aramco's downstream facilities. PROFIBUS PA option enables installation in intrinsically safe field instrument loops for classified area applications. All measured parameters, protection status, and fault history are readable via the communication interface.
Saudi Predictive Maintenance Context
Saudi Aramco's Reliability-Centred Maintenance (RCM) programme, SABIC's Asset Integrity Management, and SEC's maintenance frameworks increasingly require data-driven motor health monitoring. The DWE-4's event logging, thermal state recording, and starting profile history provide the data inputs required for predictive maintenance decisions — identifying motors with degrading insulation, bearing overheating, or supply quality problems before they cause unplanned outages. Razz Middle East provides DWE-4 configuration services and data integration support for Saudi predictive maintenance programmes.
Technical Specifications
Full specifications for the DWE-4-S4-MT
- Motor Range
- 15 kW to 1000+ kW
- Protection Functions
- overload, unbalance, phase loss, thermistor, ground fault, over/under voltage, starting profile
- Communication
- Modbus RTU + PROFIBUS DP (optional)
- Event Log
- last 8 fault events with timestamps
- THD Monitoring
- optional module
- Supply Voltage
- 24 V DC or 110–240 V AC
- Standard
- IEC 60947-4-1, IEC 60255
- Mounting
- Panel cutout or DIN Rail
Key Features & Benefits
- Advanced protection: voltage, power factor, harmonic monitoring
- PROFIBUS DP and Modbus RTU communication
- 8-event fault history with timestamps
- Starting current profile recording
- Thermal state and restart inhibit function
- Predictive maintenance data outputs
Industrial Applications in Saudi Arabia
- Critical Aramco processing plant motor protection
- SABIC asset integrity management motors
- SWCC desalination large pump protection
- SEC power plant auxiliary motor starters
- Predictive maintenance programme motors
- PROFIBUS-equipped DCS plant MCCs
Industrial Supplier in Saudi Arabia
Get a Quote for the WEG DWE-4 Advanced Electronic Motor Protection Relay
We respond within 4 business hours. Send model DWE-4-S4-MT for competitive pricing in SAR with delivery across Saudi Arabia and the GCC.
Frequently Asked Questions — DWE-4-S4-MT
Common questions from buyers in Saudi Arabia and the GCC
More weg Products
WEG AHF Active Harmonic Filter
AHF-100A
WEG AHF-030 Active Harmonic Filter 30A 400 V
AHF-030 400 V
WEG AHF-030 Active Harmonic Filter 30A 480 V
AHF-030 480 V
WEG AHF-050 Active Harmonic Filter 50A 400 V
AHF-050 400 V
WEG AHF-050 Active Harmonic Filter 50A 480 V
AHF-050 480 V
WEG AHF-075 Active Harmonic Filter 75A 400 V
AHF-075 400 V