Product image coming soon
phoenix-contact
Phoenix Contact TRABTECH TT 1-PE/S 230 Type 1 SPD
Model: 2800782
4-hour response · Pricing in SAR · Delivery across all KSA regions
2800782 — Phoenix Contact TRABTECH TT 1-PE/S 230 Type 1 SPD
The Phoenix Contact TRABTECH TT 1-PE/S 230 is a DIN-rail-mounted Type 1 surge protection device (SPD) for 230 V AC TN-S and TN-C-S networks, rated at 25 kA (10/350 μs) maximum impulse current (Iimp) per IEC 61643-11 Type 1 classification and tested to the 10/350 μs lightning-stroke current waveform that represents the energy of a direct or near-direct lightning strike on the building lightning protection system. The Type 1 classification places the TRABTECH TT 1-PE/S at the highest energy tier of LV surge protection, intended for installation at the main LV panel incomer — immediately downstream of the energy-limiting class of SPD exposure, before any downstream distribution that would be damaged by the full 10/350 μs stroke energy. The SPD uses a spark-gap-based technology (rather than the MOV technology of Type 2 devices) to handle the high-energy 10/350 μs waveform without degradation, providing a durable long-service-life device suitable for Saudi industrial environments where the surge protection at the main incomer must remain reliable for the 25–30 year life of the building's electrical installation.
The TRABTECH TT 1-PE/S is designed for TN-S systems (separate PE and N conductors) and TN-C-S systems (PEN conductor in the MV/LV transformer, then split to PE and N at the main LV panel), which are the standard earthing system configurations in Saudi Arabia per Saudi Electrical Code (SEC) and IEC 60364. In a TN-S system, the SPD is connected between L-PE and N-PE, providing both common-mode and differential-mode protection paths. The series impedance (Z) of the spark-gap discharge path is lower than that of an MOV at equivalent peak current, resulting in a lower voltage protection level during the 10/350 μs stroke — important because the panel equipment voltage withstand (Uw) is typically 4 kV or 6 kV at the main panel incomer level, and the Type 1 SPD must clamp below this level to protect the downstream panel equipment and the Type 2 SPD that follows in the protection cascade.
In Saudi Arabia, Type 1 SPD installation is mandatory per IEC 62305-4 (Protection against lightning — Electrical and electronic systems within structures) at the main LV panel of any building with an external lightning protection system (LPS), and recommended by IEC 62305-4 for buildings without an LPS but in high-risk lightning zones — which includes the majority of Saudi industrial buildings in the Eastern Province and Jubail area. Saudi Aramco's GI-0476 (Surge Protection of Instrumentation and Control Equipment) requires Type 1 SPD installation at the main LV incomer of all process facility electrical buildings, and ARAMCO's Third Party Technical Audit teams verify SPD installation as part of pre-startup inspection checklists. The TRABTECH TT 1-PE/S meets GI-0476 requirements for main-incomer Type 1 protection and carries both IEC 61643-11 test reports and CE declarations for ARAMCO HSE and SEC approval submissions. SABIC's engineering standards for new petrochemical plant electrical rooms at Jubail IV require Type 1 SPD at the main LV incomer per IEC 62305 compliance, making the TRABTECH TT 1-PE/S a standard item in SABIC Jubail expansion electrical panel BOM.
Razz Middle East stocks the TRABTECH TT 1-PE/S in both 230 V (single-phase TN-S) and 400 V (three-phase TN-S) variants in Riyadh and Jeddah. Our team provides complete Type 1 to Type 3 SPD system design per IEC 62305-4 and ARAMCO GI-0476, including: lightning risk assessment per IEC 62305-2, SPD energy coordination between Type 1 (Iimp 25 kA) and Type 2 (Imax 40 kA) and Type 3 (Imax 5 kA) devices to verify that energy sharing does not overload any device, and SPD protection level cascade confirmation. All TRABTECH TT 1-PE/S supplies include Phoenix Contact CE declarations, IEC 61643-11 test reports, and SASO import conformity documentation for Saudi Customs clearance.
Technical Specifications
Full specifications for the 2800782
- Nominal System Voltage
- 230 V AC (TN-S)
- Impulse Current (Iimp)
- 25 kA (10/350 μs)
- Max Discharge Current (Imax)
- 50 kA (8/20 μs)
- Voltage Protection Level (Up)
- <1.5 kV
- SPD Type
- Type 1 (IEC 61643-11)
- Technology
- Spark gap
- Network
- TN-S / TN-C-S
- Standard
- IEC 61643-11 Type 1 / IEC 62305-4
Key Features & Benefits
- Type 1 IEC 61643-11 classification with 25 kA (10/350 μs) impulse current rating provides the highest energy tier of LV surge protection at the main panel incomer.
- Spark-gap technology handles the 10/350 μs lightning stroke energy waveform without MOV-style degradation, ensuring 25–30 year operational life at the Saudi main incomer.
- Meets ARAMCO GI-0476 requirements for Type 1 main-incomer SPD in all process facility electrical buildings — ARAMCO Third Party Audit teams verify SPD installation pre-startup.
- IEC 62305-4 mandatory installation trigger: any Saudi building with an external LPS must have Type 1 SPD at the main LV panel incomer to prevent stroke energy from reaching downstream equipment.
- Compatible with Phoenix Contact VAL-MS 230 Type 2 coordination — energy-sharing cascade between TRABTECH (Type 1) and VAL-MS (Type 2) verified by Phoenix Contact application engineering.
- Required in SABIC Jubail IV new electrical room main LV incomer per IEC 62305-3 and SABIC engineering standard for new petrochemical plant electrical installation.
Industrial Applications in Saudi Arabia
- Main LV incomer Type 1 SPD for ARAMCO process facility electrical buildings (GOSPs, gas-compression stations, NGL units) per GI-0476 compliance.
- Main LV panel incomer surge protection for SABIC Jubail IV petrochemical expansion electrical room LV switchboards.
- Type 1 main incomer SPD for NEOM smart-city infrastructure main electrical buildings at Sharma, NEOM Bay, and OXAGON facilities with external LPS.
- LV incomer surge protection for SEC grid medium-voltage/low-voltage substation auxiliary building main panels in the Saudi national grid expansion program.
- Type 1 SPD in Type 1 → Type 2 → Type 3 cascade system for comprehensive ARAMCO field panel lightning protection per IEC 62305-4.
- Main LV panel incomer protection for Vision 2030 large commercial development main electrical rooms (Diriyah, KAEC, Amaala) with lightning protection systems.
Industrial Supplier in Saudi Arabia
Get a Quote for the Phoenix Contact TRABTECH TT 1-PE/S 230 Type 1 SPD
We respond within 4 business hours. Send model 2800782 for competitive pricing in SAR with delivery across Saudi Arabia and the GCC.
Frequently Asked Questions — 2800782
Common questions from buyers in Saudi Arabia and the GCC
More phoenix-contact Products
Phoenix Contact CLIPLINE UK 10N Power Terminal Block
3044185
Phoenix Contact CLIPLINE UK 35N Heavy Power Terminal Block
3044199
Phoenix Contact CLIPLINE UT 2.5 Feed-Through Terminal Block
3044148
Phoenix Contact PLC-RSC-24DC/21 Interface Relay Module
2966170
Phoenix Contact QUINT-PS/1AC/24DC/10 Power Supply
2938597
Phoenix Contact QUINT-PS/1AC/24DC/20 Power Supply
2938740